Electrician to Check Solar wiring in Attic

Jobs

Ocoee FL

Description

City inspection identified several discrepancies and I need to have these resolved. Here is an extract of those items: Comments: NEC 110.21 The label shall be of sufficient durability to withstand the environment involved. No hand written allowed, No paint, No label of paper NEC 690.54 Rated ac output current and the nominal operating ac voltage. INFORMATION missing Voltage and Current NEC 110.21 The label shall be of sufficient durability to withstand the environment involved. No hand written allowed, No paint, No label of paper Make sure all raceway are properly secured and supported in the attic for next inspection NEC 110.12 Unused opening It was left in AC Disconnecting NEC 352.44 Expansion Fittings for PVC conduit shall be installed to compensate thermal expansion and contraction... in PVC conduit coming down from soffit Need qualified individual to take care of these immediately.